EA900II 6KVA~10KVA online UPS is an on-line double-conversion UPS with input power factor correction (PFC), output power factor 0.9 offering high levels of reliability and protection for IT systems, telecommunications equipment and mission critical systems, ensuring maximum power reliability. Besides sufficient runtime as backup power, EA900II UPS (long time model)can be fitted with matching battery extension packs for long runtime applications; Besides some standard features of normal UPS, it is able to bear wide input voltage in harsh environment, and support 50/60Hz frequency conversion mode, and optional N+X redundancy parallel function is also available.

Characteristics

  • High frequency and true double-conversion
  • DSP digital control technology
  • Input power factor correction (PFC)
  • Wide input voltage range (110V ~ 300V)
  • Output power factor 0.9
  • Cold start
  • Auto sensing frequency
  • ECO mode operation for energy saving
  • Selectable output voltage via LCD
  • 50 Hz / 60 Hz frequency conversion mode available
  • Selectable battery low voltage via LCD
  • Power-on self test
  • Advanced battery management (ABM)
  • Short circuit and overload protection
  • Automatic charging in OFF mode
  • Fan speed auto control when loads varies
  • Standard RS232 communication port
  • Optional USB / SNMP communication port
  • Optional emergency power off (EPO)
  • Optional extension battery bank
  • Optional built-in isolation transformer
  • Optional manual bypass
  • Optional N+X redundancy parallel

Technical Specifications

MODEL

EA906II

EA9010II

Capacity

6 KVA / 5400 W

10 KVA / 9000 W

INPUT


Rated voltage

208 V / 220 V / 230 V / 240 Vac

Voltage range

Half load (110 ~ 300) ± 5 Vac

Full load (160 ~ 300) ± 5 Vac

Frequency

40 ~ 70 Hz (auto-sense)

Power factor

≥ 0.99

Bypass voltage range

160V ~ rated output voltage + 32V

OUTPUT


Voltage

208 V / 220 V / 230 V / 240 Vac (settable via LCD)

Voltage regulation

± 1%

Frequency

45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50/60 Hz  ± 0.2 Hz (battery mode)

Waveform

Sinusoidal

Crest factor

3:1

Harmonic distortion

≤ 2% (linear load); ≤ 5% (non-linear load)

Transfer time

0 ms

Overload capability

105% ~ 125%: transfer to bypass in 3 mins;

125% ~ 150%: transfer to bypass in 30 s;

>150%: transfer to bypass in 100 ms

EFFICIENCY


Mains mode

≥ 92%

Battery mode

≥ 91%

ECO mode

≥ 98%

BATTERIES


DC voltage

192 V

Inbuilt battery of standard model

16×7 Ah

16×9 Ah

Charging current

Standard model

1 A


Long time model

1 A / 3 A / 5 A / 8 A

Recharge time

8 h

ALARM


Utility failure

4 s per beep

Low battery

1 s per beep

Overload

1 s twice beep

UPS fault

Long beep

COMMUNICATIONS


RS232 (standard), USB ( optional)

Supports Windows® 98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10

SNMP (optional)

Power management from SNMP manager and web browser

OTHERS


Humidity

20 ~ 90% RH @ 0 ~ 40℃ (non-condensing)

Noise level

≤ 55 dB (1m)

Dimensions (mm) W×D×H

262 × 514 × 455 (H), 262 × 514 × 735 (S)

Packaged dimensions (mm) W×D×H

365 × 605 × 610 (H), 390 × 625 × 937 (S)

Net weight (kg)

22.1 (H), 64.1 (S)

22.8 (H), 70.8 (S)

Gross weight (kg)

25.2 (H), 72.2 (S)